Main features

Rapid and Continuous Detection of Water Activity (aw) in Oil Accurate Measurement of Water Content (ppm) in Oil Measuring lubricating oil, hydraulic oil and insulating oil Calibration Procedure for Parameters of Various Oils Long-term stable operation in harsh environment Convenient local calibration function 

Summarize

Power transformers and reactors are valuable assets in the power industry. Real-time monitoring of trace moisture in insulating oil plays a vital role in the safe operation of these valuable assets. Because the existence of moisture will reduce the breakdown voltage of insulating oil and increase dielectric loss, accelerate the degradation and aging of polymer insulation materials, thus reducing the various properties of the insulation system. In serious cases, it will cause insulation breakdown and partial discharge, affecting the safe operation of the power system. Similarly, for large-scale continuous operation equipment and heavy machinery equipment, real-time monitoring of moisture in lubricating oil and hydraulic oil plays an irreplaceable role in ensuring the normal operation of these key equipment. The existence of moisture will destroy oil film, cause corrosion of metal parts, make lubricating oil or hydraulic oil invalid, shorten the service life of oil, and even cause unplanned shutdown of large machinery, causing serious safety accidents and economic losses.

Technical parameter 

Water activity

Measuring range: 0 ~1aw Measurement accuracy:±0.02aw(at 0~0.6aw);± 0.03 aw(at 0.6aw~ 0.9aw);± 0.04 aw(at 0.9aw~1aw ).
Response time (typical): < 1 minute

Moisture in oil


Measurement range: 0…500 ppm (for mineral transformer oil) Measurement accuracy: ±10%

Temperature


Measurement Range: ‐ 40~80 ℃
Accuracy (at+25 c): ±0.2
Operating temperature: ‐ 40~+60
Digital Signal:RS485 Modbus-RTU (RS232 Optional)、4-20mA
Analog signal:4mA~20mA, 0~20mA, resistor load < 500Ω Measuring interface:G1/2 "ISO or G1/2" NPT Probe material: 316 stainless steel Power supply:9V~36V DC

Application field

Insulating oil in power industry Industrial Machinery Lubricating Oil and Hydraulic Oil Oil from other industries, turbine oil, gearbox oil